4.4.3.9.
HEATING CIRCUIT
basis
During the time switch programme is active, for the heating circuit, the parameter 710 (comfort
setpoint) is considered for the heating circuit.
If you wish the boiler stays in minimum during the reduced mode (reduced mode does not mean that
device stops, it will work if there is a heat request) you can set the minimum conditions and provide the
boiler works at minimum level. For doing this, you can adjust the reduced setpoint (parameter 712 under
The minimum level for the parameter 712 is the parameter 714. Those parameters are linked to each
other. For instance, you can decrease the parameter 710 till the parameter 712 and 712 to 714 (frost
protection setpoint) in the same manner.
Please see the examples below.
As a factory setting, the setpoints below are shown in the controller.
Under these circumstances, t
Rev: RINNAI Service manual (English)
Date:14/05/2019
To take care of when operating on time switch program
83