2.4.3 Communication parameters for DE1 variable speed starters

PNU
ID
Access right
RUN
P-12
140
RUN
P-34
162
RUN
P-35
163
RUN
P-36
164
RUN
Table 3: Communication parameters for DE1
Designation
ro/rw
rw
Local Process Data
Source
rw
PDP-Address
rw
Modbus Baud rate
rw
Modbus RTU0 COM
timeout
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
Value range
Description
0, 1, 2, 3, 4,
Local Configuration of Command and
9, 10, 11, 13
Reference Sources
• 0: Terminal Control. The drive responds
directly to signals applied to the control
terminals.
• 1: Uni-directional Keypad Control. The
drive can be controlled in the forward
direction only using an internal/external or
remote Keypad
• 2: Bi-directional Keypad Control. The drive
can be controlled in the forward and
reverse directions using an internal/
external or remote Keypad. Pressing the
keypad START button toggles between
forward and reverse.
• 3: Modbus Control.Control via Modbus RTU
communication.
• 4: CANOpen
• 9: SmartWire Device Control and speed ref.
• 10: SmartWire Device Control and terminal
speed ref.
• 11: Terminal Control and SmartWire
Device speed ref.
• 12: not permissible
• 13: SmartWire Device Control and speed
ref. Digital input sets enable
1 - 63
PDP-Address
Unique drive address in a communication
network.
0, 1, ..., 4
Modbus Baud rate
0: 960 Bit/s
1: 19.2 kbit/s
2: 38.4 kbit/s
3: 57.6 kbit/s
4: 115.2 kbit/s
Modbus RTU0 COM Timeout
Time between a communication loss and the
resulting action. Setting 0 disables the action
after communications trip.
t: indicates the drive will trip if time exceeded.
r: indicates the drive will ramp to stop if time
exceeded.
• 0: no action
• 1: t 30 ms
• 2: t 100 ms
• 3: t 1000 ms
• 4: t 3000 ms
• 5: r 30 ms
• 6: r 100 ms
• 7: r 1000 ms
• 8: r 3000 ms
2 Modbus RTU
2.4 Communication parameters
DS
0
1
4
0
17