2 Modbus RTU
2.6 Operating mode Modbus RTU
2.6.5.3 Current (ID 8)
2.6.5.4 Torque (ID 9)
2.6.5.5 Output power (ID 10)
2.6.5.6 Digital inputs (ID 11)
34
The current is specified with one decimal place.
Example: 34 ≙ 3.4 A.
The motor torque is specified with one decimal place.
Example: 1000 ≙ 100.0 %
The output power is specified in kW with one decimal place.
Example: 53 ≙ 5.3 kW
This value indicates the digital inputs' state.
The lowest bit indicates the state of DI1.
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com