3 Parameter
3.3 Parameters for DC1...E1 variable speed starters
3.3 Parameters for DC1...E1 variable speed starters
Modbus-
Para-
Parameter name
Register
meter
20
P0-01
Analog Input1
21
P0-02
Analog Input2
40
P0-03
Frequency Reference
43
P0-07
Motor Voltage
23
P0-08
DC-Link Voltage
24
P0-09
Heatsink Temperature
25
P0-10
t-Run (h)
26
P0-10
t-Run (min/sec)
39
P0-20
T-Controlboard
36
P0-26
kWh Meter
37
MWh Meter
29
P0-30
Serial Number 4
30
P0-30
Serial Number 3
31
P0-30
Serial Number 2
32
P0-30
Serial Number 1
129
P-01
f-max
130
P-02
f-min
131
P-03
t-acc
132
P-04
t-dec
133
P-05
Stop Mode
134
P-06
EnergyOptimizer
135
P-07
Motor Nom Voltage
136
P-08
Motor Nom Current
137
P-09
Motor Nom Frequency
138
P-10
Motor Nom Speed
139
P-11
V-Boost
140
P-12
Local ProcessData Source
141
P-13
Application Mode Macro
142
P-14
Password
143
P-15
DI Config Selec
144
P-16
AI1 Signal Range
54
Table 20: Parameters for DC1...E1 variable speed starters
Access
rw/ro
ro
ro
ro
ro
ro
ro
ro
ro
ro
ro
ro
ro
ro
ro
ro
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
Scaling
RUN/
STOP
RUN
4096 ≙ 100.0 %
RUN
4096 ≙ 100.0 %
RUN
RUN
230 ≙ 230 V
RUN
230 ≙ 230 V
RUN
40 ≙ 40 °C
RUN
1 ≙ 1
RUN
300 ≙ 3.00 s
RUN
40 ≙ 40 °C
RUN
100 ≙ 10.0 kWh
RUN
100 ≙ 100 MWh
RUN
1 ≙ 1
RUN
1 ≙ 1
RUN
1 ≙ 1
RUN
1 ≙ 1
RUN
3000 ≙ 50.0 Hz
RUN
3000 ≙ 50.0 Hz
RUN
300 ≙ 3.00 s
RUN
300 ≙ 3.00 s
RUN
1 ≙ 1
RUN
1 ≙ 1
STOP
230 ≙ 230 V
RUN
100 ≙ 10.0 A
STOP
50 ≙ 50.0 Hz
RUN
1 ≙ 1
RUN
100 ≙ 10.0 %
STOP
1 ≙ 1
RUN
1 ≙ 1
RUN
1 ≙ 1
STOP
1 ≙ 1
RUN
1 ≙ 1
Value range
0 - 1000
0 - 1000
-16384 - 16383
0 - 500
0 - 1000
-10 - 150
0 - N/A
0 - N/A
0 - N/A
P-02 - 5 x P-09
0.0 Hz - P-01
0.00 s - 600 s
0.00 s - 601 s
0 - 3
0 - 1
0 / 20 V - U
e
0.25 I
- I
e
e
25 Hz - 500 Hz
0 / 200 rpm - 30000 rpm
0.0 % Ue - f (FS)
FS1: 25 % U
e
FS2: 20 % U
e
FS3: 15 % U
e
FS4: 10 % U
e
0 - 13
0 - 65535
0 - 17
0 - 6
Data
format
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16