Eaton PowerXL DA1 Communications Manual page 36

Modbus rtu for variable frequency drives/variable speed starters
Hide thumbs Also See for PowerXL DA1:
Table of Contents

Advertisement

2 Modbus RTU
2.6 Operating mode Modbus RTU
Error no.
Device series
dec
hex
DA1, DC1, DE1
00
00
DA1, DC1, DE1
01
01
DA1, DC1, DE1
02
02
DA1, DC1, DE1
03
03
DA1, DC1, DE1
04
04
DA1, DC1, DE1
05
05
DA1, DC1, DE1
06
06
DA1, DC1, DE1
07
07
DA1, DC1, DE1
08
08
DA1, DC1, DE1
09
09
DA1, DC1, DE1
10
0A
DA1, DC1, DE1
11
0B
DA1, DC1, DE1
12
0C
DA1, DC1, DE1
13
0D
DA1, DC1, DE1
14
0E
DA1, DC1, DE1
15
0F
DA1, DE1
16
0A
DA1, DC1, DE1
17
11
DA1, DC1, DE1
18
12
DA1, DC1, DE1
19
12
DA1, DC1...E1
20
14
DA1
21
15
DA1, DC1...E1
22
16
DA1, DC1...E1
23
17
DA1, DC1...E1
24
18
DA1
25
19
DA1
26
1A
DA1, DC1...E1
29
1D
DA1
30
1E
DA1
31
1F
DA1
32
20
DA1
33
21
DA1
32
Fault word
Table 11: Fault messages
Message
Possible cause
(display on DA1, DC1)
The enable signal for the drive is not active (this is not an error message).
Stop
Shown for P0-13 if there are no messages in the error register.
no-Flt
Excessively high braking current
OI-b
Thermal overload on braking resistor.
OL-br
Overcurrent at variable frequency drive output
O-I
Motor overload.
I. t -trP
Overcurrent (Hardware)
PS-trp
Overvoltage in DC link
O. V olt
Undervoltage in DC link.
VVolt
Overtemperature at heat sink.
O-t
Under-temperature
V-t
The parameters' default settings have been loaded.
P-dEf
Ext Fault/Warning
E-trip
Communication error with an external operating unit or with a PC
SC-ObS
Excessively high DC link voltage ripple
FlT-dc
Incoming power phase failure (only for devices with a three-phase power supply)
P-LOss
Overcurrent at output
h O-I
Malfunctioning heat sink thermistor.
Th-flt
Error in internal memory
dAtA-F
The analog input's input current does not fall within the specified range.
4-20 F
Error in internal memory
dAtA-E
The customer's settings for the parameters have been imported.
V-dEf
Motor PTC thermistor overtemperature
F-Ptc
The device's internal fan is experiencing a fault
FAn-F
The measured ambient temperature exceeds the specified value.
O-hEAt
Maximum permissible torque exceeded.
O-torQ
Only active if brake control is enabled in hoisting gear mode (P2-18 = 8).
U-torQ
The torque produced before the hoisting gear's mechanical brake is enabled falls
below the set threshold.
Device output fault
OUt-F
Internal STO circuit fault
Sto-F
No communication between the encoder module and the variable frequency drive
Enc-01
The calculated motor speed is different from the measured motor speed
Enc-02
SP-Err
The motor speed and the PPR value entered in P6-06 do not match
Enc-03
Channel A fault
Enc-04
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerxl dc1Powerxl de1

Table of Contents