3 Parameter
3.1 Parameters for DA1 variable frequency drives
Modbus
Para-
Parameter name
register
meter
101
P1-01
f-max
102
P1-02
f-min
103
P1-03
t-acc
104
P1-04
t-dec
105
P1-05
Stop Mode
106
P1-06
EnergyOptimizer
107
P1-07
Motor Nom Voltage
108
P1-08
Motor Nom Current
109
P1-09
Motor Nom Frequency
110
P1-10
Motor Nom Speed
111
P1-11
V-Boost
112
P1-12
Local ProcessData Source
113
P1-13
DI Config Select
114
P1-14
Password
201
P2-01
f-Fix1
202
P2-02
f-Fix2
203
P2-03
f-Fix3
204
P2-04
f-Fix4
205
P2-05
f-Fix5
206
P2-06
f-Fix6
207
P2-07
f-Fix7
208
P2-08
f-Fix8
44
Access
rw/ro
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
Scaling
RUN/
STOP
RUN
3000 ≙ 50.0 Hz
RUN
3000 ≙ 50.0 Hz
RUN
300 ≙ 30.0 s
RUN
300 ≙ 30.0 s
RUN
RUN
STOP
230 ≙ 230 V
STOP
1 ≙ 0.1 A
STOP
50 ≙ 50 Hz
RUN
1500 ≙ 1500 rpm
STOP
-1 ≙ Auto
0 ≙ Disabled
1 ≙ 0.1 %
STOP
STOP
RUN
RUN
3000 ≙ 50.0 Hz
RUN
3000 ≙ 50.0 Hz
RUN
3000 ≙ 50.0 Hz
RUN
3000 ≙ 50.0 Hz
RUN
3000 ≙ 50.0 Hz
RUN
3000 ≙ 50.0 Hz
RUN
3000 ≙ 50.0 Hz
RUN
3000 ≙ 50.0 Hz
Value range
Data
format
P1-02 - (5 x P1-09)
U16
(max.: 500.0 Hz /
30000 rpm)
0.0 Hz - P1-01
U16
0.00 s - 6000 s
U16
0.00 s - 6000 s
U16
0, 1, 2, 3, 4
U16
0, 1
WORD
0 - U
U16
e
(0.1 - 1) x I
U16
e
10 Hz - 500 Hz
U16
• 0
U16
• 200 - 30000 rpm
• 0: Auto
S16
• 0 - 30.0 % of P1-07
0 - 13
U16
0 - 21
U16
0 - 30000
U16
P1-02 (min: 0 Hz / 0 rpm) -
U16
P1-01 (max: 500.0 Hz /
30000 rpm)
P1-02 (min: 0 Hz / 0 rpm) -
U16
P1-01 (max: 500.0 Hz /
30000 rpm)
P1-02 (min: 0 Hz / 0 rpm) -
U16
P1-01 (max: 500.0 Hz /
30000 rpm)
P1-02 (min: 0 Hz / 0 rpm) -
U16
P1-01 (max: 500.0 Hz /
30000 rpm)
P1-02 (min: 0 Hz / 0 rpm) -
U16
P1-01 (max: 500.0 Hz /
30000 rpm)
P1-02 (min: 0 Hz / 0 rpm) -
U16
P1-01 (max: 500.0 Hz /
30000 rpm)
P1-02 (min: 0 Hz / 0 rpm) -
U16
P1-01 (max: 500.0 Hz /
30000 rpm)
P1-02 (min: 0 Hz / 0 rpm) -
U16
P1-01 (max: 500.0 Hz /
30000 rpm)