Enable; Data Format - Eaton PowerXL DA1 Communications Manual

Modbus rtu for variable frequency drives/variable speed starters
Hide thumbs Also See for PowerXL DA1:
Table of Contents

Advertisement

2 Modbus RTU
2.3 RJ 45 interface

2.3.1 Enable

2.3.2 Data format

12
DA1
The start signal is sent via the bus.
DC1
If using Modbus, there must always be a high signal at DI1.
+24 V
1
2
DI1
Figure 4: Enable signal for bus mode in DC1 variable frequency drives
DE1
If using Modbus, there must always be a high signal at DI1.
+10 V
1
+10 V
Figure 5: Enable signal for bus mode in DE1 variable speed starters
DA1
When using DA1 variable frequency drives, the data format can be selected
using parameter P5-04.
The default setting is as follows:
No parity
1 start bit
1 stop bit
8 data bits
DC1, DE1
The data format is fixed for DC1 variable frequency drives and DE1 variable
speed starters and cannot be changed.
No parity
1 start bit
1 stop bit
8 data bits