Display ID
Access right
RUN
P5-05
505
P5-06
506
P5-07
507
Designation
ro/rw
rw
Timeout –
Communications
dropout
rw
Response in the event of
a communications
dropout
rw
Ramp via fieldbus
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
Value
Description
range
Timeout
With an active communication link, if a valid telegram
is not received by the drive within the period set with
this parameter, the drive will react as set in P5-06.
0, 1, 2, 3
Modbus communication loss error
Possible values:
• 0: Switch off
• 1: Ramps down to a full stop and is switched off.
• 2: Ramps down to a full stop; no fault message.
• 3: Ramps to fixed frequency 8 (P2-08).
0, 1
Fieldbus Ramp Control
Possible values:
• 0: OFF. Ramps are controlled from internal drives
parameters
• 1: ON. Ramps are controlled by the fieldbus.
2 Modbus RTU
2.4 Communication parameters
DS
2
0
0
15