Parameters For De1 Variable Speed Starters - Eaton PowerXL DA1 Communications Manual

Modbus rtu for variable frequency drives/variable speed starters
Hide thumbs Also See for PowerXL DA1:
Table of Contents

Advertisement

3.4 Parameters for DE1 variable speed starters

Modbus
Display
Parameter name
Register
20
P0-01
Analog Input1
23
P0-08
DC-Link Voltage
24
P0-09
Heatsink Temperature
25
P0-10
t-Run (h)
26
P0-10
t-Run (min/sec)
129
P-01
f-max
130
P-02
f-min
131
P-03
t-acc
132
P-04
t-dec
133
P-05
Stop Mode
134
P-06
EnergyOptimizer
135
P-07
Motor Nom Voltage
136
P-08
Motor Nom Current
137
P-09
Motor Nom Frequency
138
P-10
Motor Nom Speed
139
P-11
V-Boost
140
P-12
Local ProcessData Source
141
P-13
Last fault
142
P-14
Password
143
P-15
DI Config Select
144
P-16
AI1 Signal Range
145
P-17
AI1 Gain
146
P-18
AI1 Invert
147
P-19
DI3 Logic
148
P-20
f-Fix1
149
P-21
f-Fix2
150
P-22
f-Fix3
151
P-23
f-Fix4
152
P-24
Digital Reference Reset Mode
153
P-25
DCBrake
154
P-26
t-DCBrake@Stop
155
P-27
DCBrakeVoltage
156
P-28
f-DCBrake@Stop
157
P-29
Switching Frequency
Table 21: Parameters for DE1 variable speed starters
Access
rw/ro
ro
ro
ro
ro
ro
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
ro
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
rw
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
3.4 Parameters for DE1 variable speed starters
Scaling
RUN/
STOP
RUN
4096 ≙ 100.0 %
RUN
230 ≙ 230 V
RUN
40 ≙ 40 °C
RUN
1 ≙ 1
RUN
300 ≙ 3.00 s
STOP
3000 ≙ 50.0 Hz
STOP
3000 ≙ 50.0 Hz
RUN
300 ≙ 3.00 s
RUN
300 ≙ 3.00 s
RUN
1 ≙ 1
STOP
1 ≙ 1
STOP
230 ≙ 230 V
STOP
100 ≙ 10.0 A
STOP
50 ≙ 50 Hz
STOP
1 ≙ 1
RUN
100 ≙ 10.0 %
RUN
1 ≙ 1
STOP
RUN
1 ≙ 1
STOP
1 ≙ 1
STOP
1 ≙ 1
RUN
10 ≙ 1
STOP
1 ≙ 1
STOP
1 ≙ 1
STOP
3000 ≙ 50.0 Hz
STOP
3000 ≙ 50.0 Hz
STOP
3000 ≙ 50.0 Hz
STOP
3000 ≙ 50.0 Hz
RUN
1 ≙ 1
STOP
1 ≙ 1
RUN
100 ≙ 10.0 s
RUN
100 ≙ 10 %
RUN
3000 ≙ 50 Hz
STOP
1 ≙ 1
3 Parameter
Value range
Data
format
0 - 1000
0 - 1000
-10 - 150
P-02 - 300 Hz
U16
0 - P-01
U16
0.1 - 300 s
U16
0.1 - 300 s
U16
0, 1
U16
0, 1
U16
50 - 500 V
U16
(10 - 100 %) x I
U16
e
20 - 300 Hz
U16
0
U16
200 - 15000 rpm
0.0 - 40.0 %
U16
0 - 13
U16
U16
0 - 65535
U16
0-9
U16
0- 3
U16
0.10 - 2.500
U16
0, 1
U16
0, 1
U16
P-02 – P-01
U16
P-02 – P-01
U16
P-02 – P-01
U16
P-02 – P-01
U16
0, 1, 2, 3
U16
0, 1, 2, 3
U16
0 - 10 s
U16
0 - P-07
U16
0 - P-01
U16
0, 1, ..., 5
U16
57

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerxl dc1Powerxl de1

Table of Contents