9. Starting with one side, align one half of the extension rod stopper on the safety cover and align it
with the screw holes.
10. Once aligned, insert the screws and secure the stopper in place.
11. Continue with the remaining half of the stopper.
OFF
12. Once one side is complete, install the remaining stopper.
13. Close the front door. See "Closing a Front Door" on page 22.

Emergency Stop Switch

The emergency stop switch is housed on the front door. To facilitate maintenance on the switch, you
will need access to both the internal and external sides of the front door.
The bus capacitor discharge time is 15 minutes. Before starting any maintenance, switch power off,
wait for more than 15 minutes, and check for residual voltage with a meter etc., to avoid a hazard of
electrical shock.
WARNING!
!
Read the "Safety Instructions" on page ix on the first at the beginning of this manual before
performing any service on the components. Ignoring safety instructions may result in injury,
damage or death.
CAUTION!
!
D
ANGEROUS VOLTAGE LEVELS MAY BE PRESENT FOLLOWING DISCONNECTION
CABINET UNTIL A REASONABLE PERIOD OF TIME HAS ELAPSED
D
,
EATH
SERIOUS INJURY
Maintenance Manual
ON
ON
OFF
Figure 50. Installing the Extension Rod Stoppers
,
OR HARDWARE DAMAGE CAN RESULT IF CAUTION IS NOT TAKEN
.
40
Maintenance