3.4.1 Panel Mount

CAUTION:
Figure 3-6 illustrates the standard OMNI 7000 flow computer's panel mount configuration. All
dimensions are the same for the OMNI 4000 except for the depth, which is 9.5 inches
(241.3 mm).
To safely install a panel mount, follow these instructions:
1.
Verify that the panel, cabinet, or rack used
to house the flow computer is a bonded
metal surface and is connected to an Earth
Ground.
2.
Confirm that the mounting panel meets
specifications, including thickness, and will
support the weight of the flow computer.
Go to Section 8 for technical
specifications.
3-5
OMNI 4000/7000 Installation Guide – Rev H
A maximum system configuration of the OMNI 4000/7000 dissipates
approximately 29 W, including transducer loop power, which causes an internal
temperature rise of 27 °F (15 °C) over the ambient temperature.
The flow computer should not be mounted in a cabinet or panel where the inside
ambient temperature will exceed 131 °F (55 °C).
Figure 3-6: OMNI 7000 Panel Mount Configuration
Based on flow computer weight, the minimum recommended thickness of the
panel or plate used for mounting is 3/16 inch (4.8 mm).
If providing additional rear panel support before installation, the minimum
recommended thickness is 1/8 inch (3.2 mm).