Omni 4000 Series Installation Manual page 143

Flow computer
Hide thumbs Also See for 4000 Series:
Table of Contents

Advertisement

OMNI 4000/7000 Installation Guide – Rev H
14.
Press the Apply Low function key to
complete the Low adjustment or the Abort
function key to discard.
15.
Adjust the Signal Generator or configure
the Transmitter, whichever is connected,
to output the appropriate HI value
according to the selected calibration units.
High values are 20.00 mA for a
4‒20 mA input, 5V for a 1‒5V input,
and 150 ohms for an RTD input.
Confirm that the Live Input (mA/Ohms)
16.
field value in the Apply High Input
Source screen is close to the applied
value from the field transmitter or
signal generator.
If the value is not close to the applied
value, check:
The wiring is connected to the correct
channel.
The hardware jumper settings.
17.
Wait 20 to 30 seconds for the readings to
stabilize.
While the Applied Input Value? field is
18.
highlighted, press OK.
19.
Using the numeric keypad, enter a value
that exactly matches the value at the field
transmitter or the signal generator.
Press OK.
5-5
Calibration

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Omni 4000 Series

This manual is also suitable for:

7000 series

Table of Contents