Calibrate Using Omniconnect; Analog Inputs - Omni 4000 Series Installation Manual

Flow computer
Hide thumbs Also See for 4000 Series:
Table of Contents

Advertisement

16.
a. If you have trouble calibrating the
output channel, reset the channel by
clicking the Defaults function key and
attempt to calibrate the channel again.
b. Press the Yes function key to
finalize the calibration of the output
channel.
c. Press the No function key to
discard the calibration changes.
Continue calibrating additional output
17.
channels by repeating Steps 1 through 16.
5.2

Calibrate Using OMNICONNECT

The Calibration menu can be accessed through the Diagnostics button on the Home ribbon. If
there is a project-specific requirement to reset all input and output channels before calibration,
perform the steps in Section 7.1.2 Reset Multiple Channels before calibrating.
For inputs and outputs:

5.2.1 Analog Inputs

To calibrate analog input channels that are configured in the flow computer, follow these
instructions:
1.
Click the Diagnostics button in the Home
ribbon to open the Diagnostics tree in the
left panel.
2.
Click Calibration in the left panel to
display its configuration settings in the
screens on the right.
5-9
OMNI 4000/7000 Installation Guide – Rev H
Click the Restore button any time after starting a calibration. This command
restores the calibration constants to the values they were when the calibration
was initiated.
Click the Apply Defaults button any time after starting a calibration to:
Reset the calibration constants to their default non-calibrated values.
Clear the adjustments for a selected channel.
Calibration
®