Omni 4000 Series Installation Manual page 189

Flow computer
Hide thumbs Also See for 4000 Series:
Table of Contents

Advertisement

Configure each Load Resistor as required for instrument installation as indicated in Figure A-8
(refer to Figure 3-32 through Figure 3-34 for wiring examples).
OUT = Externally installed load resistor of 250Ω to 600Ω
250Ω = On-board load resistor is installed in the current loop.
500Ω = On-board load resistor is installed in the current loop.
MODULE
ADDRESS
1
2
3
4
5
6
Figure A-8: HART Address and Load Resistor Jumpers
A.8
Digital I/O Terminal Board Setup
Each DT module requires a specific unique address of 1 through 3. Position the Address
Selection Switches as indicated in the Address Selection table shown in Figure A-9.
Set the COMM LINK TERMINATION Switch to the IN position:
If the DT module is the only Digital Terminal module connected to the flow computer
If the DT module is positioned at the end of the Comm Link bus. Refer to Digital
Terminal Board #3 in Figure 3-20.
Otherwise, set the switch to the OUT position.
Page A-11
OMNI 4000/7000 Installation Guide – Rev H
HT/HM LABEL
AD1
AD2
AD3
Jumper Settings
LEDs
NETWORK 1
LOAD
RESISTOR
OUT
O
250
500O
SELECT APPROPRIATE
LOAD RESISTOR

Hide quick links: