OMNI 4000/7000 Installation Guide – Rev H
10.
Use the front panel to key in the value that
appears on the ammeter:
a. Select the Measured Output
(mA)? field.
b. Press OK.
c. Enter the value.
d. Press OK again or the Accept
function key.
11.
If needed, press the Abort function key to
cancel the calibration.
To continue to the 20-mA calibration
screen, press the Apply Low
function key.
The next screen shows the Output Value
(mA) field default of 20.00.
12.
Wait 20 to 30 seconds for the readings to
stabilize.
Note the value indicated on the ammeter.
13.
Use the front panel of the flow computer to
14.
key in the value displayed by the
ammeter:
a. Select the Measured Output
(mA)? field.
b. Press OK.
c. Enter the value.
d. Press OK again or the Accept
function key.
15.
If needed, press the Abort function key to
cancel the calibration.
To continue to the Finalize Calibration
screen, press the Apply HI function key.
5-8
Calibration