Depending on the selections made in the Equipment List in General Setup
(Section 4.10.1 General Setup), not all four items of the Meter Runs may be
described in these instructions.
Meter Runs for flow computers that are configured for gas applications will have
different configuration settings.
To assign input to a meter run, follow these instructions:
1.
In the Configure tree in the left panel,
expand the first Meter Run to see
all items.
2.
Select Flowmeter - Pulse Type to display
its configuration options.
3.
On the Setup tab, select a Flow I/O Point
using the drop-down box.
Fill in the remaining information in the
4.
Flowmeter screens for each tab.
Press F1 to access
OMNICONNECT Help for
assistance.
4-64
OMNI 4000/7000 Installation Guide – Rev H
Configuration