Output Calibration - Omni 4000 Series Installation Manual

Flow computer
Hide thumbs Also See for 4000 Series:
Table of Contents

Advertisement

20.
Press the Apply HI function key to
complete the span adjustment or the
Abort function key to discard.
After pressing the Apply HI function key,
21.
the Finalize Calibration? screen displays.
a. If you have trouble calibrating the
input channel, reset the channel by
pressing the Defaults function key;
then attempt to calibrate the
channel again.
b. Press the Yes function key to
finalize the calibration of the input
channel.
c. Press the No function key to
discard the calibration changes.
22.
Continue calibrating additional input
channels as needed by repeating
these steps.

5.1.2 Output Calibration

To calibrate the 4‒20 mA output channels, follow these instructions:
1.
a. From the main menu of the front
panel, select Utilities and press OK.
b. Select Calibration, press OK.
c. Select Output Calibration.
2.
Press OK to enter the edit mode of the
Selected Output? field.
5-6
OMNI 4000/7000 Installation Guide – Rev H
Calibration