Process Image - WAGO 750 Series Manual

Fieldbus independent i/o modules. pulse width output module
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

12 •
750-511, /000-002 [2DO 24V DC 0.1A / Pulse Width]

Process Image

2.1.2.7
Process Image
Using the I/O module 750-511 or 750-511/000-002, a 6 byte input and output
process image can be transferred to the fieldbus coupler / controller via two
logical channels. The setting of the On/Off times occur in the four output
bytes (D0, D1) or (D2, D3). The four input bytes (D0, D1, D2, D3) and the
status bytes (S0, S1) are not used for the On/Off time settings.
Attention
The representation of the process data of some I/O modules or their variations
in the process image depends on the fieldbus coupler/-controller used. Please
take this information as well as the particular design of the respective
control/status bytes from the section "Fieldbus Specific Design of the Process
Data" included in the description concerning the process image of the
corresponding coupler/controller.
S0
D0
D1
S1
D2
D3
The programming of the On/Off times occur with the resolution of 10 bits.
The five LSB of the 16 bit are not defined. In the table these bits are
represented with a 'X'. The indication of the hexadecimal and the decimal
numerical values in the table considers the condition ' 0 ' for the first five low
order bits in each case. If these five bits accept the condition ' 1 ', the decimal
numerical value is higher around 31, than indicated in the table.
The MSB will hold the sign and is preset to the null state.
Input data
Status byte 0
X (no evaluation)
X (no evaluation)
Status byte 1
X (no evaluation)
X (no evaluation)
Pulse duty
Units
factor
[%]
100,0
1023
50,0
511
25,0
255
0,1955
2
0,0977
1
0,0
0
C0
Control byte 0
D0
On/Off time 1 (low Byte)
D1
On/Off time 1 (high Byte)
C1
Control byte 1
D2
On/Off time 2 (low Byte)
D3
On/Off time 2 (high Byte)
750-511, 750-511/000-002
numerical value
binary
'0111.1111.111X.XXXX'
'0011.1111.111X.XXXX'
'0001.1111.111X.XXXX'
'0000.0000.010X.XXXX'
'0000.0000.001X.XXXX'
'0000.0000.000X.XXXX'
Output data
hex.
dec.
0x7FE0
32736
0x3FE0
16352
0x1FE0
8160
0x0040
64
0x0020
32
0x0000
0
WAGO-I/O-SYSTEM 750
I/O Modules