750-511, /000-002 [2Do 24V Dc 0.1A / Pulse Width]; View; Variations; Description - WAGO 750 Series Manual

Fieldbus independent i/o modules. pulse width output module
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

8 •

750-511, /000-002 [2DO 24V DC 0.1A / Pulse Width]

View

2.1.2 750-511, /000-002 [2DO 24V DC 0.1A / Pulse Width]
2-Channel Pulse Width Output Module DC 24 V
2.1.2.1
View
Function
Fig. 2.1.2-1: 2-Channel Pulse Width Output Module 750-511
2.1.2.2

Variations

Item-No.
750-511
750-511/000-002 2DO 24V DC 0,1 A/
2.1.2.3

Description

The Pulse width output module 750-511 or 750-511/000-002 is able to
modulate Signed-Integer values to pulse width modulated 24 V output signals
with a constant pulse frequency or periodic time. The On/Off time is given by
values of 16 bits.
The module has two output channels and enables the direct wiring of two
loads with ground (earth) to the connections DO 1 or DO 2, the common 0 V
ground potential and ground (earth), if necessary.
The outputs are short-circuit-protected.
The basic frequency or the period can be parameterized for both channels of
the module together. For the module 750-511 the initial pre-programmed base
frequency is 250 Hz, for the module 750-511/000-002 it is 100 Hz.
13 14
A
DO 1
C
B
D
13 14
DO 1
+
+
-
-
750-511
Designation
2DO 24V DC 0,1 A/
Pulse Width /250 Hz
Pulse Width /100 Hz
Function
DO 2
Data contacts
DO 2
24V
0V
Power jumper contacts
Description
2-Channel Pulse Width Output Module
DC 24 V
2-Channel Pulse Width Output Module
DC 24 V
g051100e
WAGO-I/O-SYSTEM 750
I/O Modules

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-511

Table of Contents