The output bytes of channel 1 (D0, D1) are used for the register values.
2.1.2.9.3

Example 750-511

The following examples illustrate the register read and write modes. The
values are binary. In order to make things easier, only the process data of
channel 1 is mentioned.
Read register 2
The module is in process date exchange:
Control byte C0
Register read access is available when bit 7 is set and the register address is
entered in the control byte.
Control byte C0
You can reactivate the process data exchange if you erase bit 7.
Control byte C0
WAGO-I/O-SYSTEM 750
I/O Modules
750-511, /000-002 [2DO 24V DC 0.1A / Pulse Width]
Bit 7
Bit 6
Bit 5
REG
X
register address
register communication
This constant must be set to zero.
Output byte D1
'0XXX.XXXX'
'XXXX.XXXX'
Status byte S0
Input byte D1
'0XXX.XXXX'
Output byte D1
'1000.0010'
'XXXX.XXXX'
Status byte S0
Input byte D1
'0XXX.XXXX'
'XXXX.XXXX'
'1000.0010'
Output byte D1
'0XXX.XXXX'
'XXXX.XXXX'
Status byte S0
Input byte D1
'1000.0010'
'0XXX.XXXX'
Parameterizing the Period / Pulse frequency
Status byte 0
Bit 4
Bit 3
X
X
X
A0 = 0, A1 = 1: register 2
A0 = 1, A1 = 1: register 3
REG = 0: process data communication
REG = 1: register communication
Output byte D0
'XXXX.XXXX'
Input byte D0
'0000.0000'
'0000.0000'
Output byte D0
'XXXX.XXXX'
Input byte D0
'XXXX.XXXX'
'0000.1111'
'1010.0000'
Output byte D0
'XXXX.XXXXX'
Input byte D0
'0000.1111'
'1010.0000'
'0000.0000'
'0000.0000'
Bit 2
Bit 1
Bit 0
X
A1
A0
Remark
processing active
value in register 2
e.g. 4000µs (250 Hz)
(0x0FA0)
Remark
acknowledge
process data
exchange
• 15