20 •
750-511/000-001 [2DO 24V DC 0,1A/Frequency/2kHz]
Display Elements
The field side supply voltage of 24 V for the output module is derived from
adjacent I/O modules or from a supply module. The supply voltage for the
field side is made automatically through the individual I/O modules by means
of power jumper contacts.
Warning
The maximum current of the internal power jumper contacts is 10 A. When
configuring the system it is important not to exceed the maximum/sum
current. However, if such a case should occur, another supply module must
be added.
Note
Use an appropriate supply module (e.g. 750-602) if an electrically isolated
voltage supply is required!
The special module 750-511/000-001 can be used with all couplers/controllers
of the WAGO-I/O-SYSTEM 750 (except for the economy types 750-320, -
323, -324 and -327).
This description is valid for the XXXX3A04... hardware and software
versions. The version is specified in the manufacturing number, which is part
of the lateral marking on the module.
2.1.3.3
Display Elements
A
Fig. 2.1.3-2: Display
Elements
LED Chan
A
gree
13 14
n
A
C
C
B
D
C
g041402x
gree
n
Meaning
State
nel
Function
1
DO 1
Function
2
DO 2
Function
No internal data bus
off
communication.
Internal data bus
on
communication.,
normal operation
No internal data bus
off
communication.
Internal data bus
on
communication.,
normal operation
WAGO-I/O-SYSTEM 750
I/O Modules