Conettix Universal Dual Path Communicator
8.2.2
Primary Power Fail Delay
Default: 60
Selections: 0 to 255 (minutes)
When primary power is missing or low (brownout condition), the B465 waits for the minutes
you enter here to create a primary power fail event.
USB Menu Location
[4] System Configuration > [2] Primary Power Supervision > [2] Primary Power Fail Delay
8.2.3
Primary Power Fail sends reports
Default: Enabled
Selections:
–
–
The B465 waits the time set in the Primary Power Fail Delay parameter before sending AC Fail
reports.
Notice!
UL 864 requirement for commercial fire
To comply with UL864 requirements for commercial fire systems, set this parameter to
Enabled.
USB Menu Location
[4] System Configuration > [2] Primary Power Supervision > [3] Primary Power Fail sends
reports
8.2.4
Primary Power Fail sets Trouble Output
Default: Disabled
Selections:
–
–
The B465 waits the time set in the Primary Power Fail Delay parameter before setting the
trouble output.
Notice!
UL 864 requirement for commercial fire
To comply with UL864 requirements for commercial fire systems, set this parameter to
Enabled.
USB Menu Location
[4] System Configuration > [2] Primary Power Supervision > [4] Primary Power Fail sets
Trouble Output
8.3
Battery Supervision
8.3.1
Battery Monitoring
Default: Enabled
Selections:
–
–
The battery voltage must be below 12.1 volts for 16 seconds before the B465 creates a low
battery event. It takes between 10 and 60 seconds to sense a missing battery.
Bosch Security Systems, Inc.
Enabled - the B465 sends primary power fail and primary power restoral reports
Disabled - the B465 sends primary power fail and primary power restoral reports.
Enabled - when primary power fails, the B465 sets the trouble output.
Disabled - the B465 does not set the trouble output when primary power fails.
Enabled - the B465 monitors the battery for low and missing conditions.
Disable - the B465 does not monitor the battery.
Installation and Operation Manual
System Configuration | en
2017.11 | 05 | F.01U.311.207