Application Environment - Bosch Conettix B465 Installation And Operation Manual

Universal dual path communicator
Hide thumbs Also See for Conettix B465:
Table of Contents

Advertisement

Conettix Universal Dual Path Communicator
12.1.2

Application environment

Application
Residential Burglary
Proprietary Burglary
Central Station (Bank)
Central Station (Mercantile)
Police Station Connected (Bank)
Police Station Connected (Mercantile)
Local Burglary (Bank)
Local Burglary (Mercantile)
Commercial Fire
Residential Fire
Table 12.18: Minimum standby and alarm times
Notice!
UL Commercial Burglary Application Requirements
Mount the module in the B465 enclosure. If the unit is used in a commercial burglar
environment, and is enclosed in a commercial enclosure, that enclosure must be tampered.
The B465 must be mounted inside an attack resistant enclosure (D8108A) if the installation is
a local or police station connection. For Commercial Burglary applications, house all
communicators in tampered enclosures. You must wire system troubles back to the control
panel as the B46 can not be used in the D8108A enclosure.
Bosch Security Systems, Inc.
Minimum Required
Standby Time (hr)
4
4
72
4
72
24
72
24
24
24
Installation and Operation Manual
Specifications and certifications | en
Minimum Alarm Time (min)
4
N/A
N/A
N/A
30 (CUL)/15 (UL)
30 (CUL)/15 (UL)
30 (CUL)/15 (UL)
30 (CUL)/15 (UL)
30 (CUL)/5 (UL)
5 (CUL)/4 (UL)
2017.11 | 05 | F.01U.311.207
97