Conettix Universal Dual Path Communicator
SYSTEM TROUBLE Flashing (one flash) - Ethernet Trouble
Flash pattern (TX)
Flashing
Flashing (two flashes)
Flashing (three flashes)
Tab. 11.10: Ethernet LED descriptions
SYSTEM TROUBLE Flashing (two flashes) - Cellular Trouble
Heartbeat
LED
On Steady
On Steady
Bosch Security Systems, Inc.
Function
RX LED
Flashing (one flash)
Flashing (two flashes)
Installation and Operation Manual
Maintenance and troubleshooting | en
Indicates an Ethernet Network Cable open. Verify your
Ethernet connection to the B465 is secure. Also verify
the Ethernet connection is secure to your network.
Indicates an Ethernet IP Address error Verify that DHCP
is enabled if your network is assigning the IP address or
that your network administrator has setup your device
correctly. Refer to USB menu options to change/edit
your IP address.
Indicates an Ethernet DNS Lookup error. Make sure you
have an Internet connection that has access to the
world wide web.
Plug-in Status LED
N/A
Off
83
Function
Indicates the plug-in
module is missing.
Verify the plug-in
module is firmly
inserted into the
module connector.
Indicates the plug-in
module is not
recognized. Verify the
correct plug-in
module is firmly
inserted into the
module connector.
Verify the latest
firmware is installed
to support the
module you have.