100 en | Specifications and certifications
12.1.5

Required programming to meet UL 864

This section identifies the programming requirements for UL 864 Commercial Fire
applications.
Notice!
TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply
with the requirements in the Standard for Control Units and Accessories for Fire Alarm
Systems, UL 864, you must limit certain programming features or options to specific values.
Primary Power Source,
page 72
(set to AC)
Primary Power Fail Delay,
page 73
Primary Power Fail sends
reports, page 73
Primary Power Source,
page 72
(set to DC)
Primary Power Fail Delay,
page 73
Primary Power Fail sends
reports, page 73
Battery Monitoring, page
73
Battery faults send
reports, page 74
2017.11 | 05 | F.01U.311.207
Parameter
Permitted in UL
Installation and Operation Manual
Possible settings
864?
(Yes/No)
Yes
AC, DC
Yes
0 to 255 minutes 60 to 180 minutes
Yes
Enabled/Disabled Enabled - if sending
Yes
AC/DC
Yes
0 to 255 minutes 0 to 3 minutes
Yes
Enabled/Disabled Enabled - if sending
Yes
Enabled/Disabled Enabled
Yes
Enabled/Disabled Enabled - if sending
Conettix Universal Dual Path Communicator
Settings permitted
in UL 864
AC - when using
transformer as
source.
report from B465,
disabled if using
relay outputs to
control panel
DC - when powering
from UL listed
control panel or
power supply
report from B465,
disabled if using
relay outputs to
control panel
report from B465,
disabled if using
relay outputs to
control panel