Bosch Conettix B465 Installation And Operation Manual page 109

Universal dual path communicator
Hide thumbs Also See for Conettix B465:
Table of Contents

Advertisement

Conettix Universal Dual Path Communicator
1-300-99-iii
SYSTEM TROUBLE
3-300-99-iii
SYSTEM TROUBLE (restoral)
1-301-99-iii
AC LOSS
3-301-99-iii
AC LOSS (restoral)
1-302-99-iii
LOW SYSTEM BATT
Bosch Security Systems, Inc.
Contact ID report
(i = input number, 001-004)
(t = trouble type)
Installation and Operation Manual
B465 Event
When a B465 input that is configured for
Panel System Trouble is shorted, the B465
makes a Panel System Trouble event and
sends a SYSTEM TROUBLE report.
When a B465 input that is configured for
Panel System Trouble returns to normal after
being shorted, the B465 makes a Panel
System Trouble Restoral event and sends a,
SYSTEM TROUBLE Restoral report.
When a B465 input that is configured for
Panel AC Fail is shorted, the B465 makes a
Panel AC Fail event and sends an AC LOSS
report.
When the primary power source for the
B465 fails, the B465 makes a Primary Power
Fail event and sends an AC LOSS report (iii =
000).
When a B465 input that is configured for
Panel AC Fail returns to normal after being
shorted, the B465 makes a Panel AC Fail
Restoral event and sends an, AC LOSS
restoral report.
When the primary power source for the
B465 returns to normal after failing, the
B465 makes a primary power restoral event
and sends an AC LOSS Restoral report (iii =
000).
When a B465 input that is configured for
Panel Low / missing Battery is shorted, the
B465 makes a Panel Low / missing Battery
event and sends a LOW SYSTEM BATT
report.
When the battery voltage for the B465 is
low, the B465 makes a low battery event and
sends an LOW SYSTEM BATT report (iii =
000).
Specifications and certifications | en 109
B465 Event #
2017.11 | 05 | F.01U.311.207
1
2
3
4
5