Pstn Reporting Format Compatibility; Phone Line Voltage - Bosch Conettix B465 Installation And Operation Manual

Universal dual path communicator
Hide thumbs Also See for Conettix B465:
Table of Contents

Advertisement

12
en | System overview
7
LEDs to show System Trouble (TRBL), Power (PWR), and Battery (BAT). The B46 is
compatible with the B10, and D8103 enclosures. The LEDs are visisble through a knockout in
the enclosure door.
8
and B11(R) enclosures. The default configuration for this connecter is disabled. Commercial
Burger installations require an enclosure tamper.
9
supported control panels and fire control panels for the dialer capture function.
10
control panel to communicate alarm events and control panel status to the B465. The B465
sends an applicable report to the central station receiver.
11
(Special Application 9.9 - 13.8 V).
12
Form C dry contact relay rated at 30 VDC. 0.5 A. Output 2 and Output 3 are Form A dry
contact relays rated at 30 VDC, 0.1 A. All three outputs are configurable.
13
14
secondary (backup) power source for the B465.
15
emissions.
16
use 24 VDC from a UL listed fire control panel or power supply. Or you can use a D1640 plug-
in transformer, D1640-CA plug-in transformer, or D1640-120WI wired-in transformer. These
transformers have a rating of 16.5 VAC, 40 VA.
Notice!
Commercial Fire requirement
Commercial Fire applications require that you install a D8004 Transformer Enclosure if you
are using either the D1640 or D1640-CA plug-in transformers.
3.2

PSTN reporting format compatibility

The B465 is suitable for use with of the following standard digital dialer formats:
3.2.1

Phone line voltage

The B465 simulates conventional phone lines to the control panel. The B465 supplies a
constant phone voltage of 28 VDC (control panel dialer on hook) to satisfy the control panel's
phone line monitor. The B465 phone voltage is 3 to 8 VDC when the control panel attempts to
communicate (off hook).
2017.11 | 05 | F.01U.311.207
- EXTERNAL ANNUNC connector - for the optional B46 External annunciator. The B46 uses
- TMPR connector - for the ICP-EZTS Tamper Switch. Use this tamper switch on B10(R)
- PANEL LINE 1, PANEL LINE 2 terminals - for connection to the phone line terminals of
- 1 COM 2, 3 COM 4 terminals - for inputs 1 to 4. Connect to dry contact outputs on the
- 12V AUX/COM terminal - provides 0.5 A of power at 12 VDC for auxiliary devices
- OUTPUT (RELAY) 1, OUTPUT (RELAY) 2, OUTPUT (RELAY) 3 terminals - Output 1 is a
- Heartbeat LED - shows the operational status of the B465.
- BATTERY terminals- connect a 12 V 7-18 Ah Lead Acid battery. The battery is the
- Earth Ground terminal - Used for earth ground transient protection and reduced
- 24 VDC or 16.5 VAC terminals - connect the primary power supply for the B465. You can
Modem II
Modem IIe
Modem IIIa
2
Ademco Contact ID (SIA DC-05) +10 digit account codes
Pulse 3/1, 3/1 Checksum (2300 Hz ACK Tone)
Pulse 3/1, 3/1 Checksum (1400 Hz ACK Tone)
Pulse 4/2 (2300 Hz ACK Tone)
Pulse 4/2 (1400 Hz ACK Tone)
SIA (SIA8, SIA20)
Installation and Operation Manual
Conettix Universal Dual Path Communicator