Output Wiring - Bosch Conettix B465 Installation And Operation Manual

Universal dual path communicator
Hide thumbs Also See for Conettix B465:
Table of Contents

Advertisement

Conettix Universal Dual Path Communicator
Input voltage parameters
You can determine the condition of on-board inputs 1 to 4 by measuring the voltage across the
input terminal (1 to 4) and the COM terminal. The loop wiring must be connected and the 2.21
kΩ EOL resistor must be in place and the input function programmed.
1
COM
Figure 4.8: Input terminals
Loop
Open
Normal
Shorted
Tab. 4.1: Input voltage parameters
Warning!
UL Commercial Fire requirement, do not connect multiple wires to any B465 terminal
!
If multiple wires are required, connect a single wire to the terminal then connect multiple
wires to the single wire using a wire nut or other approved method.
The graphic below is an example of multiple wire connections to a terminal.
Figure 4.9: Multiple wire connections to a terminal example
Callout ー Description
1 ー Wire nut or other means required to tie wires together as UL only allows one wire in
each terminal.
4.7.6

Output wiring

The module has three programmable outputs OUTPUT (RELAY) 1, OUTPUT (RELAY) 2, OUTPUT
(RELAY) 3. The outputs can be connected to the control panel inputs (points or zones) to
communicate the B465 status to the control panel.
Each output can be configured for one output function:
Bosch Security Systems, Inc.
2
3
COM
4
1
System Trouble
AC Fail
Installation and Operation Manual
Voltage range
Greater than 3.7 VDC, but less than 5.0 VDC
Greater than 2.0 VDC, but less than 3.0 VDC
Greater than 0.0 VDC, but less than 1.3 VDC
Installation | en
25
2017.11 | 05 | F.01U.311.207