Control Panel To B465 Wiring For Dialer Capture - Bosch Conettix B465 Installation And Operation Manual

Universal dual path communicator
Hide thumbs Also See for Conettix B465:
Table of Contents

Advertisement

Conettix Universal Dual Path Communicator
SDI2 Device Bus connector
The SDI2 Device Bus terminal connector is for future use. Do not connect devices to it.
Notice!
SDI2 Device Bus connector not tested by UL
The SDI2 Device Bus terminal connector is for future.
4.7.2

Control panel to B465 wiring for dialer capture

Use the PANEL LINE 1 and PANEL LINE 2 terminals for the dialer capture function.
Both lines run at 28 VDC and support DTMF (Contact ID), Pulse 3/1, Pulse 4/2, and SIA
reporting formats.
You can configure the B465 to remove power from the panel line terminals when there is a
B465 communication failure event. This causes a trouble event at the connected control
panels configured for supervised phone lines.
The connection of the phone lines for Commercial Fire applications must be within the same
room, in conduit, and within 20 ft of the connected control panel for ULC-S559 installations.
Use 14-24AWG wire to connect the B465 PANEL LINE 1 and PANEL LINE 2 terminals to a fire
control panel or intrusion control panel phone line terminals.
Refer to the following figure for wiring information.
Figure 4.4: Panel to dialer capture wiring
Callout ー Description
1 ー Fire control panel or intrusion control panel
2 ー B465
3 ー Optional second panel phone connection depending on equipment ( panel phone line 2)
4 ー Primary phone connection (panel phone line 1)
5 ー Internal Ground (AUX Power negative or internal Common) required for Commercial Fire
6 ー Control panel EOL resistor (required for supervision with callout #7)
7 ー Optional for local B465 troubles
Bosch Security Systems, Inc.
1
PSTN
PSTN
AUX/COM
ZONE INPUT
2
1
Installation and Operation Manual
2
Y
24 VDC
or
16.5 VAC
BATTERY
+
-
16.5VAC
NC C NO
C
BATTERY
RELAY 2
RELAY 1
7
5
6
Installation | en
MODULE 1
X
MODULE
RELEASE
COMMUNICATION MODULE 1
ETHERNET
100BASE-T
LINK
USB
SYSTEM TROUBLE
TX
TX
RX
SDI2
POWER
PWR
Device Bus
BATTERY
R Y G B
INPUTS
2.2 k
End of
Line Resistors
PANEL
PANEL
1 COM 2
3 COM 4
LINE 1
LINE 2
T
R
T
R
NO
C
NO
12V
1
COM
2
3
COM
4
AUX COM
PNL LINE 1
PNL LINE 2
RELAY 3
3
4
2017.11 | 05 | F.01U.311.207
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents