Input Configuration; Input 1 (To 4) - Bosch Conettix B465 Installation And Operation Manual

Universal dual path communicator
Hide thumbs Also See for Conettix B465:
Table of Contents

Advertisement

78
en | Input Configuration
9

Input Configuration

9.1

Input 1 (to 4)

Default: Disabled
Selections:
USB Menu Location
[5] Input Configuration > [1,2,3,4] Input 1 (to 4)
2017.11 | 05 | F.01U.311.207
Disabled - no reports for short or open on this input.
Panel System Trouble - when the sensor loop for this input is shorted, the B465 sends a
Contact ID 300, System Trouble report. When the sensor loop is open, the B465 sends a
Contact ID 371, Protection Loop Open report.
Panel AC Fail - when the sensor loop for this input is shorted, the B465 sends a
Contact ID 301, AC Loss report. When the sensor loop is open, the B465 sends a
Contact ID 371, Protection Loop Open report.
Panel Low Battery - when the sensor loop for this input is shorted, the B465 sends a
Contact ID 302, Low System Battery report. When the sensor loop is open, the B465
sends a Contact ID 371, Protection Loop Open report.
Fire Alarm - when the sensor loop for this input is shorted, the B465 sends a
Contact ID 110, Fire alarm report. When the sensor loop is open, the B465 sends a
Contact ID 373, Fire Trouble report.
Fire Trouble - when the sensor loop for this input is shorted or open, the B465 sends a
Contact ID 373, Fire Trouble report.
Fire Supervisory - when the sensor loop for this input is shorted, the B465 sends a
Contact ID 200, Fire Supervisory report. When the sensor loop is open, the B465 sends a
Contact ID 373, Fire Trouble report.
Burglary Alarm - when the sensor loop for this input is shorted, the B465 sends a
Contact ID 130, Burglary alarm report. When the sensor loop is open, the B465 sends a
Contact ID 371, Protection Loop Open report.
Burglary Trouble - when the sensor loop for this input is shorted, the B465 sends a
Contact ID 380, Sensor Trouble report. When the sensor loop is open, the B465 sends a
Contact ID 371, Protection Loop Open report.
Installation and Operation Manual
Conettix Universal Dual Path Communicator
Bosch Security Systems, Inc.

Hide quick links:

Advertisement

Table of Contents
loading