CHANGE OF THE SAFETY MODULE
8 Change of the Safety Module
Danger
A change of the safety module is displayed by the control in the COMBIVIS with status 61 „ERROR
safety mod. changed". The user must confirm the change by writing of parameter de.38 "serial
number safety module" with the entered value. Only then the error can be reset.
The parameters for acknowledge the safety module change are password protected. The work can
be carried out only by qualified persons.
CAUTION
34
Electric Shock
Before working with the unit disconnect it from mains. Check the iso-
lation from supply by measurements in the unit. Await min. 15 minutes
until the capacities of the DC link are discharged.
Working after the change
The change may be done only by qualified persons. Check the safety
functions and error responses and generate an acceptance report after
the change.