Description Of The Terminals; Figure 1: Description Of The Terminals; Table 6: Mechanical Specification Of Terminal Strip X2B - KEB COMBIVERT F6 Instructions For Use Manual

Functional safety
Hide thumbs Also See for COMBIVERT F6:
Table of Contents

Advertisement

DESCrIPTION OF THE TErMINALS

4 Description of the Terminals
Terminal
The individual channels are designed potential-free, so 24V and 0V can be connected. The inputs are de-
signed by way that safety switchgear units with test pulses (OSSD signals) can be connected. The signals
are not evaluated, they are only filtered. The OSSD test interval is limited to 10 ms.
Figure 1:
Description of the Terminals
Stranded wire (rigidly and flexibly)
Ferrule plastic collar
Table 6:
Mechanical specification of terminal strip X2B
Safety module type 1
PIN
Name
1 / 2
STO1+
3 / 4
STO1-
5 / 6
STO2+
7 / 8
STO2-
9 / 10
SBC1+
11 /12
SBC1-
13 /14
SBC2+
15 / 16
SBC2-
17 / 18
Status STO
19 / 20
Status SBC
PE
Mechanical specification of terminal strip X2B
Terminal cross-section
0.14...1.5 mm²
0.14...1 mm²
Function
Input
STO channel 1
Input
STO channel 2
Input
SBC channel 1
Input
SBC channel 2
Output STO
Output SBC
For H6 drive modules:
Earth, make sure to connect the mains
earth !
Stripping length
26-18 AWG
12 mm
21

Hide quick links: