WAGO-SPEEDWAY 767
767-5203 Serial Interface (RS-232, RS-422/-485)
7.3.1

Connection Mode "Digital Output"

Table 33: Overview of adjustable parameters for the digital outputs

Parameter
Connection mode
Designation
Output value
Process image value
Signal Inversion
Substitute value strategy This releases the substitute value or the last output value in cases such as
Substitute value
Manual Operation
Diagnostic Simulation
Restart mode
Actuator
Manual
Version 1.1.0
Description
Mode display
Electronic marking field (max. 40 characters)
The output state is indicated in this field.
This field indicates the value of the output process image for this output.
When manual operation is activated, the field becomes a checkbox.
Activate the checkbox to output the state "1" on the output independent
of the control unit.
Here you can release the current process value as an inverted output
value.
Checkbox deactivated*:
Output signal is output as shown in the process image
Checkbox activated:
Output signal is output inverted as shown in the process image
a fieldbus interruption. You have the following options:
- Switch to substitute value*
- Keep last value**
Enter the process value that is output in case of error. In case of error
(e.g., fieldbus interruption), the value is used with the "Switch to
substitute value" substitute value strategy.
Checkbox deactivated:
0*
Checkbox activated:
1
Activate the checkbox to define the output value independent of the
control unit. When manual operation is activated, the field for the
process image value becomes a checkbox for the manual operation
value.
Activate the checkbox to switch diagnostic simulation on. When the
simulation is switched on, the fields for the diagnoses become
checkboxes.
Set the restart behavior of an enabled output if the output has been
disabled due to the "Overtemperature" diagnosis. You have the
following options:
- Delayed*
After the time set has elapsed ("Restart delay, actuator"), the output is
switched on again automatically.
- Diagnosis acknowledgement
The output is only switched on after acknowledging the diagnostic
message. Acknowledge the diagnostic message from the higher-level
control unit or PLC. The respective coupler manual specifies which
fieldbus couplers this functionality supports.
Information about diagnostic acknowledgement:
When using fieldbus couplers that do not support the diagnostic
acknowledgement, disabled outputs may remain OFF.
Parameterizing
59