9.2

Error detection

9.2
Error detection
The fault can be caused by mechanical or electrical malfunctions.
LED
The occurrence of an error state is signalized by the lighting up of the red LED H14 or
H24 on the front side of the housing.
NOTE!
In case of warnings or errors without error reactions, the LEDs H14 or H24 blink
„Malfunction". Only error messages with error reaction will be signalized by constant
lighting up.
7-segment display In the status error the error numbers are shown in the display. Depending on the state of
bit No. 16 in parameter P135.1 (further information see parameter handbook b maXX
5000 add-on module MOD) all error messages (with/without error reaction) or warnings
are displayed.
The display of an error code starts therewith, that „F" is displayed for 1.5 s. Then the four
characters of the error code are displayed. The separate characters are displayed for
about 0.8 s, interrupted by a short break. If there are other errors, these are displayed in
the same manner. The procedure is repeated as soon as all errors were displayed.
Example: Error 702 and 2418 are existing:
Start
Error
display
Figure 22:
For further information on the subjects of error messages and error numbers, see „Pa-
rameter manual b maXX 5000".
Operating
Furthermore the error message is shown in the operating software:
software ProDrive
NOTE!
The controller software version and the operating software version must be compat-
ible to use ProDrive with all functions.
82
Instruction handbook b maXX 5000 add-on module MOD
Document No.: 5.19015.01
of 90
7-segment display: errors and warnings
End