12 Click to the icon „Drive management".
In addition window „Drive manager dialog" appears.
(2)
Figure 18:

Ramp function generator - window with drive manager dialog

13 Select in scroll list (1) the operation mode „Speed control"
14 Switch on Pulse enable and No Quickstop
15 Click on button „Start" (2) in drive management dialog.
The motor should rotate with 10 % of the maximum speed.
Control:
16 Choose in ProDrive Navigation „Configuration/Encoder/Encoder 1".
17 In this window:
Speed smoothed: approx. 10 %
NOTE
Do not click on button „Stop" (3) in the drive management dialog! First check, whether
the speed actual value is transmitted to encoder 2 via the incremental encoder emu-
lation IEE.
Instruction handbook b maXX 5000 add-on module MOD
Commissioning/Operation
(3)
Document No.: 5.19015.01
6
(1)