7.8

Controller timeout

7.7.1

Actual Value Watchdog

m The actual value watchdog is configured by Modbus register 203
m A value of 0 deactivates the watchdog
m A value not equal 0 corresponds with the watchdog time in ms
m The watchdog can be configured in state Pre-Operational only
m The watchdog timer is restarted with the configured value in ms with every reading of
m After the watchdog timer expires, bit 1 of the status word is set to 1.
m The error bit can be reseted via control word bit 1
7.7.2

Set Value Watchdog

m The set value watchdog is configured by Modbus register 204
m A value of 0 deactivates the watchdog
m A value not equal 0 corresponds with the watchdog time in ms
m The watchdog can be configured in state Pre-Operational only
m The watchdog timer is restarted with the configured value in ms with every writing of
m After the watchdog timer expires, bit 2 of the status word is set to 1.
m The error bit can be reseted via control word bit 2
7.8
Controller timeout
The controller checks internally whether the mapped parameters still read or written cy-
clically from/to the Modbus registers. The corresponding error bit is set in the status word
if the controller recognizes that the parameters are not read or written.
Status word bit 3: Actual values from the controller are not read from the Modbus register
Status word bit 4: Set values from the controller are not written to the Modbus register
The error bits can be reseted by the corresponding bits in the control word.
Control word bit 3: Resets actual value errors
Control word bit 4: Resets set value errors
7.9

General errors

Status word bit 5 is set to 1 in case an error occurs that is not displayed by another
register. The corresponding b maXX error code can be read via Modbus register 200 -
201.
Bit 5 in status word can be reseted by bit 5 in control word.
58
Instruction handbook b maXX 5000 add-on module MOD
Document No.: 5.19015.01
of 90
the status word in state Operational. The monitoring starts with the first reading of the
status word in state Operational.
the control word in state Operational. The monitoring starts with the first writing of the
control word in state Operational.