9.3
Error handling
9.3.2

Error messages

In the column „Reaction" the reaction of the system to the error is shown:
m „adjustable" = the error reaction can be set via ProDrive (Window „Drive management",
IEE
Error
Error description
No.
424
Configuration error,
further details in status P172.2:
n Bit10:
IEE add-on module is not avail-
able
n Bit11:
Start after zero pulse selected
and encoder is not an incremen-
tal encoder
425
Run time error,
further details in status P172.2:
n Bit 8:
Output frequency to high
add-on module IEE cannot gen-
erate the required number of
pulses
Cause:
The product from set value
change and no. of increments is
too high
n Bit 9:
Error in set value source
IEE switches off, because of an
error in set value source
84
Instruction handbook b maXX 5000 add-on module MOD
Document No.: 5.19015.01
of 90
toolbar button „Error reaction").
Reaction
adjustable
adjustable
Troubleshooting
n Bit10:
Use controller with IEE add-on module
n Bit11:
Use incremental encoder for source encoder or
select option „Start: immediately".
n Bit 8:
Reduce no. of increments of IEE or reduce the
drive speed, from which the set value is generated
or reduce the set speed from the higher-level con-
trol according following formula:
f = n*N
f. no. of increments per sec
n: Speed [revolution per sec.]
N: No. of increments [inc/rev]
n
max
Frequency limit=500 kHz,
with N=10 000 inc/rev:
n
50 rev/s
3000 rev/min
max
n Bit 9:
Check set value source and correct problem
= f
/N
max
Baumüller Nürnberg GmbH