5.19 MULTI-FUNCTION OUTPUT TERMINALS
n095 : Speed Coincidence Frequency / Frequency
Detection Level
Speed coincidence is used to control an output contact at terminals MA or MB (with respect to ter-
minal MC), or terminals P1, P2 & PC, when selected by n057, n058 and n059.
n057, n058 or n059
The output contact will close, dependent upon the data programmed into n057, n058 or n059 . See
the appropriate figure below for operation.
A. Speed at Set Frequency
(setting: n057, n058 or n059 = " 2 ")
DETECTION WIDTH
±2Hz
OUTPUT
FREQUENCY
FREQUENCY
AGREED
SIGNAL
C. Frequency Detection – High
(setting: n057, n058 or n059 = " 5 ")
FREQUENCY
DETECTION
LEVEL (Hz)
(n095)
OUTPUT
FREQUENCY
FREQUENCY
DETECTION
SIGNAL
RELEASE WIDTH
±2Hz
Frequency
Reference
ON
RELEASE WIDTH
—2HZ
ON
Continued
B.
Frequency Detection – Low
(setting: n057, n058 or n059 = " 4 ")
RELEASE WIDTH
FREQUENCY
FREQUENCY
DETECTION
SIGNAL
5-30
Factory setting: 0.0 Hz
Range: 0.00 to 400.0 Hz
Data 2 , 4 or 5
FREQUENCY
+2HZ
DETECTION
LEVEL (Hz)
(n095 )
ON