Honeywell ESSER IQ8Control C Installation Instruction page 48

Fire alarm
Hide thumbs Also See for ESSER IQ8Control C:
Table of Contents

Advertisement

Fire Alarm Control Panel IQ8Control C / M
RS485 interface
An external device, such as an LCD display panel, can be connected to the A/B terminals via the RS485 interface.
A
RS485
-
+
A
external device
Fig. 39: RS485 interface
RS 485-1
Connection interface – total length max. 1000 m
A/B
X32
closed
 RS 485 termination resistance activated
open
 RS 485 termination not activated
RS 485-2
A/B
Do not alter position of the jumpers!
X33/35
Do not connect terminals!
X34
48
X33
X35
1
1
2
2
3
3
X34
X32
1
1
2
2
3
3
B
A
B
RS485
1
2
B
The RS485 BUS must be connected with an
EOL resistor at both ends of the loop.
If the FACP incl. basic module is the last
device on a loop end, the integrated EOL
resistor can be activated with the X32
jumper.
FB 798951.10.GB0 / 04.15