Fire Alarm Control Panel IQ8Control C / M
Earth fault monitoring
BR 1
Earth fault monitoring enabled (factory default = ON)
Earth fault monitoring disabled (not VdS appropriate)
Information for powered loop systems
In case of an earth fault with +U
message "U
than the required 42 V. The alarm device may not sound an alarm at full volume.
Undervoltage protection (U
BR2
Undervoltage protection activated (factory setting = ON)
The panel switches off automatically if, in case of charging, the
battery voltage is  9.5 DC.
Under voltage protection disabled
Selection of the loop voltage
BR 4
esserbus
®
loop with 27,5 V voltage
®
esserbus
PLus loop with 42 V voltage
For esserbus
devices with Part No. 80xxxx required
Damage to the system !
Mixed operation with esserbus
Selection of the Fire Alarm Control Panel
Solder jumper on the rear side of the PCP to select the CPU power supply.
BR5
Factory default of a separately delivered power supply module
(Prepared for mounting in the FACP 8000 C / M)
Operation in FACP IQ8Control C/M
32
zone
<" will be displayed for each loop. In the alarm condition, the zone voltage is lower
zone
< 9,5 V DC)
Batt
®
PLus module Part No. 804382 and appropriate loop
®
and esserbus
a ground fault message occurs and additionally the fault
®
PLus function is not possible!
Jumper BR 5 closed
ON
1 2 3
OFF
1 2 3
1
ON
2
3
1
2
OFF
3
3 2 1
3 2 1
BR5
BR5