Extension Housing For Two Batteries (Part No. 789300 / -01) - Honeywell ESSER IQ8Control C Installation Instruction

Fire alarm
Hide thumbs Also See for ESSER IQ8Control C:
Table of Contents

Advertisement

The extension housing is assembled / mounted similar to the central housing. The individual assembly steps are
described in the section "Assembling the central housing".
The following must also be observed when assembling the extension housing:
The connection pieces between the central and extension housings can be pushed into the housing only from
the rear side due to the door hinge. If an extension housing is fitted at the bottom to an already securely
installed central housing, the central housing must be removed from the assembly surface.
A separate drilling template is available for each of the two housing variants with the standard or battery rear
panel. The drilling template is enclosed in the central unit's additional pack.
The fastening holes in the mounting surface must be drilled precisely and without offset to the side. Otherwise,
use of the connecting pieces between the two housings is no longer possible in the event of major deviations.
If the extension housing with the battery rear panel is used, please note that depending on the
rechargeable batteries used, a significant weight must be supported by the fastening screws of the
extension housing. Longer 8 mm flat-head screws should always be used here.
Each housing must be separately secured with suitable fastening materials such as screws and dowels.
Attachment of the extension housing only via the connection pieces between the central and extension
housing is not permissible.

19.1 Extension housing for two batteries (Part No. 789300 / -01)

Up to 2 batteries 12 V / 24 Ah may be placed inside the lower housing part of the IQ8Control M or in the extension
housing (Part No. 789300 / -01). The required battery fastener (plastic device) is delivered with the panel
equipment.
Fig. 110: Mechanical battery
Damage to the system!
Please note that depending on the rechargeable batteries used, a significant weight must be supported
by the fastening screws of the extension housing. It is not permissible to install the rechargeable
batteries without these fastening clamps.
See Chapter 4.1.3.
FB 798951.10.GB0 / 04.15
Fire Alarm Control Panel IQ8Control C / M
Place batteries as shown and insert
fastener.
Assemble the additional battery mount 
and  .
1
2
131

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Esser iq8control m

Table of Contents