7.1.7 Technical data essernet
Operating voltage
Current consumption
Emergency operation
Connector
Network devices
Transmission speed
Required cable
Transmission
Topology
Compatibility
FB 798951.10.GB0 / 04.15
®
micro module
essernet
®
micro module 62.5 k
(Part No. 784840 / 784840.10)
: Internal via the power supply module,
+ 5 V DC
:
®
: A single essernet
micro module may be connected per FACP on the appropriate
micro module slot on the Basic module.
Observe jumper X4 / X5!
:
max. 16
:
up to 62.5 kBd
: Telephone cable
I-Y (ST) Y n x 2 x 0.8 mm,
Cable length max. 1000 m.
Other cable types such as paper-
wrapped cables, control lines (NYM) or
smaller cross-sections are not suitable.
The cable must be twisted and shielded.
The signal wires are protected against interference through connection of the
:
Token-Passing protocol similar to DIN 19245 - 1 (Profi BUS)
:
loop topology (wire-breakage und short circuit tolerance)
: essernet
®
micro module 62.5 kBd (Part No. 784840)
Do not operate hardware with index up to B2 with hardware from index
B3 in a common panel.
Fire Alarm Control Panel IQ8Control C / M
essernet
(Part No. 784841 / 784841.10)
Internal via the power supply module,
approx. 150 mA @ 12 V DC
yes
IBM type 1 max. 1000 m
between two network devices
IBM type 2 (Earth cable) max. 1000 m
between two network devices
IBM type 6 (flexible) max. 200 m
between two network devices
cable shielding.
®
micro module 500 k
+5 V DC
max. 31
up to 500 kBd
75