Fire Alarm Control Panel IQ8Control C / M
Trouble
Possible cause
Code No.
1)
Detector is soiled or damp.
012
2)
CO sensor is faulty.
1)
Air speed too high at site
of installation.
2)
Detector is soiled with
conductive substance and
013
may be installed in damp
environment.
3)
CO sensor has temporarily
left its working range (e.g.
due to oversaturation).
Short-circuit at the
014
temperature sensor.
1)
Faulty bonding of the
temperature sensor.
015
2)
First installation at a cool
place.
016
1)
Detector is soiled with a
conductive substance or
017
installed in damp
surroundings.
2)
Faulty detector.
3)
CO sensor is faulty. It is
possible that the rel.
humidity is always at a
very low value in the area
surrounding the detector.
1)
Detector is soiled with a
conductive substance or
018
installed in damp
surroundings.
2)
Faulty detector.
1) Detector is soiled with oily
substance.
019
2) CO sensor is faulty.
020
Current levels not correct on
021
loop.
Detector unable to correctly
022
activate its base circuit board.
116
1st. measure
Clean detector and check it with
programming software tools
8000.
Replace detector.
Clean detector and check it with
programming software tools
8000.
Reset detector and recheck.
Replace detector and return to
manufacture.
Adjust detector to ambient
temperature with programming
software tools 8000.
see 001
Clean detector and check it with
programming software tools
8000.
Replace detector.
Clean detector and check it with
programming software tools
8000.
Clean detector and check it with
programming software tools
8000.
Replace detector.
Check numbers of detectors,
loop resistor and loop length.
Check detector base wiring.
2nd. measure
Check the installed detector if
the surrounding area is
humid. Use protective
measures if necessary, e.g.
series 9x00 detectors: surface
mount adapter 781495 or
781497/98 uses base
adapter.
Return faulty detectors to the
manufacturer.
Using another detector type.
If the error occurs again,
return detector to
manufacturer for checking.
Replace detector and return
---
Replace detector and return
Return faulty detectors to the
manufacturer.
Replace detector and return
Return faulty detectors to the
manufacturer.
Check detector base wiring.
---
---
to manufacture.
---
to manufacture.
to manufacture.
---