Fire Alarm Control Panel IQ8Control C / M
8.2.1 Technical Data Relay module
4-relay module (Part No. 787530)
Operating voltage
Quiescent current
Fuse (F1, F2, F3, F4)
Relay (K1, K2, K3, K4)
Contact rating
Voltage
Quiescent current
consumption
Relay
Contact rating
Fuse
Compatibility
Damage to the system!
No AC voltages may be applied to the relays built-into the FACP IQ8Control. This applies also to
those relays operated in the >non-monitored< mode!
Observe Schematic wiring of inductive loads!
86
: Internal via the power supply module, + 5 V DC / +12 V DC
: approx. 10 mA @ 12 V DC
: Multifuse 1 A (for Relay K1 to K4)
: 4 programmable contacts - normally Open or normally close
(not monitored)
: max. 30 V DC / 1 A per output
3-relay module
(Part No. 787531)
:
Internal via the power supply
module, + 5 V DC / +12 V DC
:
5 mA@ 12 V DC
:
3 monitored, normally open or
normally close contacts
:
max. 30 V DC / 1 A per output
:
Multifuse 1 A (per relay)
: The Relay modules may be operated on a free selectable micro module
slot of the FACP IQ8Control.
For System 8000 fire alarm control panels the relay module may be used
as a replacement devices.
3-relay common fault module
(Part No. 787532)
Internal via the power supply module,
+ 5 V DC / +12 V DC
15 mA@ 12 V DC
2 monitored, normally open or
normally close contacts plus a
common fault relay (energized in
normal operation)
max. 30 V DC / 1 A per output
Multifuse 1 A (per relay)
FB 798951.10.GB0 / 04.15