Fire Alarm Control Panel IQ8Control C / M
1.
Open panel housing
2.
Set DIL switch S2 (1+2) on the Basic module in Pos. ON (LED V50 lits).
3.
Press reset button S1  FACP reset
4.
Wait until FACP is resetted and the display message „Servicemode" appears.
5.
Connect USB cable (Part No. 789863) to the USB-connector of the FACP IQ8Control an.
6.
Start tools 8000 software on the Service PC and select >Tools / actualize panel software<.
7.
After the firmware update the message >Update successful< appears on the Service-PC
8.
Remove USB-plug from the Basic module and set DIL-switch S2 in position OFF  the FACP IQ8Control
will be automatically resetted and returns to the normal operation mode.