Checking The Essernet ® Devices And Connections - Honeywell ESSER IQ8Control C Installation Instruction

Fire alarm
Hide thumbs Also See for ESSER IQ8Control C:
Table of Contents

Advertisement

11.3 Checking the essernet
An additional check of the essernet
(Part No. 784840.10 / 784841.10 - from index "E" onwards).
Switching on the display on the fire alarm control panel:
Press key
The display will automatically alter from indication on side 1+2. By turning the key switch (unlock keyboard) the
display is set to normal indication mode.
Display page 1
Terminal 12
Terminal 34
Fault 12 [%]
Fault 34 [%]
FtMax 12 [%]
FtMax 34 [%]
Rep. Telegr
PanelNo.
Display page 2
Level 12
Level 34
-
-
-
-
Version
PanelNo
The counters are reset when the FACP is restarted.
FB 798951.10.GB0 / 04.15
®
devices and connections
®
devices/connections can be carried out using the essernet
Test
Test
Value
Meaning
(example)
Number of telegrams received without error at terminals 1+2 of the essernet
micro module. Automatic update of the values:
1555
- essernet
- essernet
1551
Terminals 3+4 (see "Terminal 12")
Percentage display of the faulty telegrams which are received at terminals 1+2
of the essernet
0
- essernet
- essernet
0
Terminals 3+4 (see "Fault12")
Maximum percentage value of the faulty telegrams received at terminals 1+2
6
since the panel was last restarted. This function enables a measurement over a
longer period and is reset to "0" after every restart of the FACP.
8
Terminals 3+4 (see "FtMax 12")
Number of repetition requests.
4
Repetition requests for telegrams are a sign that there are faults on a module or
on the transmission path.
Display of the micro module address which has been set on the essernet
10
module. This address must correspond to the customer data of the FACP.
Value range at terminal 1+2 from 0 to 100.
Values from 10 to 100  normal operation
Values below 10  fault
33
The yellow LED onto the module lits. Furthermore the message will be
displayed as >common fault< and indicated in the display with >Sys. fault
essernet<.
66
terminals 3+4 (refer to "Level 12")
---
500000
Software V5.00R00 of the essernet
Address setting of the essernet
10
selected address in the FACP software configuration.
Fire Alarm Control Panel IQ8Control C / M
F3
®
micro module 62.5 kBd: every 45 seconds
®
micro module 500 kBd: every 10 seconds
®
micro module. Automatic update of the values:
®
micro module 62.5 kBd: every 45 seconds
®
micro module 500 kBd: every 10 seconds
®
®
module – This address must match the
6
---
- module
®
micro modules
®
®