Master Box Activation Module - Honeywell ESSER IQ8Control C Installation Instruction

Fire alarm
Hide thumbs Also See for ESSER IQ8Control C:
Table of Contents

Advertisement

9

Master box activation module

Micro module for activating a master box (MB) and alerting the relevant emergency services, such as the fire
department. With the Fire Alarm Control Panel, a connection for a master box module is integrated in the Field
device module. If a Field device module is not fitted, an MFAB control module can be used for the connection of
a master box. Up to 10 MFAB may be operated within a common FACP.
The required operation must be programmed with the service PC and Programming software tools 8000.
MFAB activation module
BR1 BR2 BR3 BR4 BR5 BR6
K 1
F 1
Fig. 80: Master box activation module
X1
64-way plug connector to micro module slot of the Basic module, Field device module or
Extension module
K1
Relay for switching the MFAB power supply, e.g., +12 V or +24 V (DC)
max. contact rating max. 30 V DC / 1 A
F1
Electronic fuse (multifuse): to reset, de-energise for approx. 30 seconds at the relevant screw
terminals on the terminal card
S1
Setting the master box activation mode:
Switch set to left
Switch set to right
S2
DIL switch to select the activation time of the MFAB (see table next Page)
BR1, BR3
Hardware adjustment of MFAB activation (see following pages).
FB 798951.10.GB0 / 04.15
Fire Alarm Control Panel IQ8Control C / M
Activation intermittent
Activation continuous
S 1
ON
S 2
X1
89