Fire Alarm Control Panel IQ8Control C / M
7.1.5 essernet
®
module
The essernet
®
module permits networking up to 31 essernet
Panel System and management systems. Additionally optional gateways are available to connect standard
devices to the network.
Fire alarm control panel
IQ8Control M
®
Fig. 62: Example - essernet
Terminal card assignment
FACP 1
1
2
3
4
5
do not connect!
6
do not connect!
Fig. 63: Connection principle (copper cable, conventional) incl. cable shielding in essernet
In a essernet
The EMI-protection / the extended EMI-protection of the LAN network must be implemented by external
EMI protection devices.
72
Indicating and operating panel
essernet
Fire alarm control panel
IQ8Control C
with different devices
FACP 2
®
you may only use essernet
®
devices, such as e.g. ESSER Fire Alarm Control
Fire alarm control panel
IQ8Control M
®
Serial
essernet
essernet
module
®
1
3
2
4
®
®
modules with the same transmission speed.
Fire alarm control panel
IQ8Control C
Management system
-Interface
®
FACP 3
essernet
module
®
3
4
FB 798951.10.GB0 / 04.15
1