Honeywell ESSER IQ8Control C Installation Instruction page 47

Fire alarm
Hide thumbs Also See for ESSER IQ8Control C:
Table of Contents

Advertisement

6.3.6 Serial interface
The serial interface on the Basic module may be configured as a TTY interface (20 mA) or as an RS485 interface.
The required interface to connect external devices is selected by the Service software tools 8000.
TTY interface
V62 V63
reversed
TxD
Polarity
A
B
A
RxD
TxD
TTY
Tx -
Tx +
Rx -
external devices
Fig. 38: TTY interface
FB 798951.10.GB0 / 04.15
These four terminals may be used for connecting an external
device, e.g. a protocol printer or the kit for a redundant
transmission path* (Part No. 784749), via the TTY interface
(20 mA).
Cable length between external device and interface
max. 1000 m.
In operation (green LED)
If wired correctly, the green LED (TxD) will blink at the
transmission frequency to provide visual indication of proper
interface wiring.
B
Reverse polarity indicator (red LED)
If the connection cables are transposed at the terminals, red
LED (Reversed polarity) will light up.
Rx +
Fire Alarm Control Panel IQ8Control C / M
*
This option may be installed inside the FACP housing with the Top-hat
rail mounting kit (Part No. 788652).
47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Esser iq8control m

Table of Contents