7.1.3 Maximum line lengths based on the total load factor of a loop
FACP
max. loop lenght
up to 700 m
800 m
900 m
1000 m
1100 m
1300 m
1500 m
1600 m
2000 m
2100 up to 3500 m
up to 700 m
800 m
900 m
1000 m
1100 m
1300 m
1500 m
1600 m
2000 m
2100 up to 3500 m
7.1.4 Technical Data loop module
Internal voltage supply
Quiescent current
(with 127 loop devices)
Emergency operation
Terminals
Recommended connecting
cable
The permitted loop length depends on the number and type of the loop devices and may differ
from the max. loop length.
max. 2 loop modules Part No. 804382 / 804382.10 / 804382.D0 per IQ8Control C as well as max.
4 or 6 modules per IQ8Control M
Part No. 78 4382 / 78 4382.10 / 78 4382.D0  loop module (esserbus
fire detectors and esserbus
the jumper on the power supply module Part No. 802426 of the FACP
Part No. 80 4382 / 80 4382.10 / 80 4382.D0  loop module (esserbus
loop module to connect Fire detectors and esserbus
required loop voltage 42 V must be selected via the jumper on the power supply module (Part No.
802426) of the FACP.
Do not exceed the max. admissible total load factor of 96 (per loop)
FB 798951.10.GB0 / 04.15
Loop 1
Loop 2
91 to 96
91 to 96
85 to 90
85 to 90
79 to 84
79 to 84
73 to 78
73 to 78
67 to 72
67 to 72
61 to 66
61 to 66
55 to 60
55 to 60
49 to 54
49 to 54
1 to 48
1 to 48
0
0
46 to 48
46 to 48
43 to 45
43 to 45
40 to 42
40 to 42
37 to 39
37 to 39
34 to 36
34 to 36
31 to 33
31 to 33
28 to 30
28 to 30
25 to 27
25 to 27
1 to 24
1 to 24
0
0
Part No. 784382 / 784382.10 /
784382.D0 (esserbus
Internal +12 V and +27,5 V
60 mA @ 12 V
yes
Telephone cable I-Y (ST) Y n x 2 x 0.8mm with special designation or
fire detection cable
Loop resistance 65  @ 1000 m loop length
(measured from terminal A+ to B+)
Total loop resistance max. 130  (measured from terminal A+ to B+)
Up to 3500 m total loop length is possible for IQ8 fire detectors or alarm
devices with consideration of the load factor
®
-transponder. The required loop voltage 27.5 V must be selected via
Fire Alarm Control Panel IQ8Control C / M
Loop 3
Loop 4
91 to 96
91 to 96
85 to 90
85 to 90
79 to 84
79 to 84
73 to 78
73 to 78
67 to 72
67 to 72
61 to 66
61 to 66
55 to 60
55 to 60
49 to 54
49 to 54
1 to 48
1 to 48
0
0
46 to 48
46 to 48
43 to 45
43 to 45
40 to 42
40 to 42
37 to 39
37 to 39
34 to 36
34 to 36
31 to 33
31 to 33
28 to 30
28 to 30
25 to 27
25 to 27
1 to 24
1 to 24
0
0
Part No. 804382 / 804382.10 /
®
)
804382.D0 (esserbus
Internal +12 V and +42 V
removable, for max. 1,5 mm
®
-transponder and alarm devices. The
Loop 5
Loop 6
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
46 to 48
46 to 48
43 to 45
43 to 45
40 to 42
40 to 42
37 to 39
37 to 39
34 to 36
34 to 36
31 to 33
31 to 33
28 to 30
28 to 30
25 to 27
25 to 27
1 to 24
1 to 24
0
0
®
PLus)
60 mA @ 12 V
yes
2
®
) loop module to connect
®
-PLus)
71